Components

The attributes of components are listed below.

Base

  • type name: base

The base type for all power-grid-model components.

Input

name

data type

unit

description

required

update

id

int32_t

-

ID of a component. The ID should be unique across all components within the same scenario, e.g., you cannot have a node with id=5 and another line with id=5.

❌ (id needs to be specified in the update query, but cannot be changed)

Steady state output and Short circuit output

name

data type

unit

description

id

int32_t

-

ID of a component, the ID should be unique across all components, e.g., you cannot have a node with id=5 and a line with id=5.

energized

int8_t

-

Indicates if a component is energized, i.e. connected to a source

Node

  • type name: node

  • base: Base

node is a point in the grid. Physically a node can be a busbar, a joint, or other similar component.

Input

name

data type

unit

description

required

update

valid values

u_rated

double

volt (V)

rated line-line voltage

> 0

Steady state output

name

data type

unit

description

u_pu

RealValueOutput

-

per-unit voltage magnitude

u_angle

RealValueOutput

rad

voltage angle

u

RealValueOutput

volt (V)

voltage magnitude, line-line for symmetric calculation, line-neutral for asymmetric calculation

p

RealValueOutput

watt (W)

active power injection

q

RealValueOutput

volt-ampere-reactive (var)

reactive power injection

Note

The p and q output of injection follows the generator reference direction as mentioned in
Reference Direction

Short circuit output

name

data type

unit

description

u_pu

RealValueOutput

-

per-unit voltage magnitude

u_angle

RealValueOutput

rad

voltage angle

u

RealValueOutput

volt (V)

voltage magnitude (line-neutral)

Branch

  • type name: branch

  • base: Base

branch is the abstract base type for the component which connects two different nodes. For each branch two switches are always defined at from- and to-side of the branch. In reality such switches may not exist. For example, a cable usually permanently connects two joints. In this case, the attribute from_status and to_status is always 1.

Input

name

data type

unit

description

required

update

valid values

from_node

int32_t

-

ID of node at from-side

a valid node ID

to_node

int32_t

-

ID of node at to-side

a valid node ID

from_status

int8_t

-

connection status at from-side

0 or 1

to_status

int8_t

-

connection status at to-side

0 or 1

Steady state output

name

data type

unit

description

p_from

RealValueOutput

watt (W)

active power flowing into the branch at from-side

q_from

RealValueOutput

volt-ampere-reactive (var)

reactive power flowing into the branch at from-side

i_from

RealValueOutput

ampere (A)

current at from-side

s_from

RealValueOutput

volt-ampere (VA)

apparent power flowing at from-side

p_to

RealValueOutput

watt (W)

active power flowing into the branch at to-side

q_to

RealValueOutput

volt-ampere-reactive (var)

reactive power flowing into the branch at to-side

i_to

RealValueOutput

ampere (A)

current at to-side

s_to

RealValueOutput

volt-ampere (VA)

apparent power flowing at to-side

loading

double

-

relative loading of the line, 1.0 meaning 100% loaded.

Short circuit output

name

data type

unit

description

i_from

RealValueOutput

ampere (A)

current at from-side

i_from_angle

RealValueOutput

rad

current angle at from-side

i_to

RealValueOutput

ampere (A)

current at to-side

i_to_angle

RealValueOutput

rad

current angle at to-side

Line

  • type name: line

line is a Branch with specified serial impedance and shunt admittance. A cable is also modeled as line. A line can only connect two nodes with the same rated voltage. If i_n is not provided, loading of line will be a nan value.

Input

name

data type

unit

description

required

update

valid values

r1

double

ohm (Ω)

positive-sequence serial resistance

r1 and x1 cannot be both zero

x1

double

ohm (Ω)

positive-sequence serial reactance

r1 and x1 cannot be both zero

c1

double

farad (F)

positive-sequence shunt capacitance

tan1

double

-

positive-sequence shunt loss factor (tan𝛿)

r0

double

ohm (Ω)

zero-sequence serial resistance

✨ only for asymmetric calculations

r0 and x0 cannot be both zero

x0

double

ohm (Ω)

zero-sequence serial reactance

✨ only for asymmetric calculations

r0 and x0 cannot be both zero

c0

double

farad (F)

zero-sequence shunt capacitance

✨ only for asymmetric calculations

tan0

double

-

zero-sequence shunt loss factor (tan𝛿)

✨ only for asymmetric calculations

i_n

double

ampere (A)

rated current

> 0

Note

In case of short circuit calculations, the zero-sequence parameters are required only if any of the faults in any of the scenarios within a batch are not three-phase faults (i.e. fault_type is not FaultType.three_phase).

Electric Model

line is described by a \(\pi\) model, where

\[\begin{split} \begin{eqnarray} & Z_{\text{series}} = r + \mathrm{j}x \\ & Y_{\text{shunt}} = \frac{2 \pi fc}{\tan \sigma +\mathrm{j}} \end{eqnarray} \end{split}\]

Transformer

transformer is a Branch which connects two nodes with possibly different voltage levels. An example of usage of transformer is given in Transformer Examples

Input

name

data type

unit

description

required

update

valid values

u1

double

volt (V)

rated voltage at from-side

> 0

u2

double

volt (V)

rated voltage at to-side

> 0

sn

double

volt-ampere (VA)

rated power

> 0

uk

double

-

relative short circuit voltage, 0.1 means 10%

>= pk / sn and > 0 and < 1

pk

double

watt (W)

short circuit (copper) loss

>= 0

i0

double

-

relative no-load current

>= p0 / sn and < 1

p0

double

watt (W)

no-load (iron) loss

>= 0

winding_from

WindingType

-

from-side winding type

winding_to

WindingType

-

to-side winding type

clock

int8_t

-

clock number of phase shift.
Even number is not possible if one side is Y(N) winding and the other side is not Y(N) winding.
Odd number is not possible, if both sides are Y(N) winding or both sides are not Y(N) winding.

>= 0 and <= 12

tap_side

BranchSide

-

side of tap changer

tap_pos

int8_t

-

current position of tap changer

(tap_min <= tap_pos <= tap_max) or (tap_min >= tap_pos >= tap_max)

tap_min

int8_t

-

position of tap changer at minimum voltage

tap_max

int8_t

-

position of tap changer at maximum voltage

tap_nom

int8_t

-

nominal position of tap changer

❌ default zero

(tap_min <= tap_nom <= tap_max) or (tap_min >= tap_nom >= tap_max)

tap_size

double

volt (V)

size of each tap of the tap changer

>= 0

uk_min

double

-

relative short circuit voltage at minimum tap

❌ default same as uk

>= pk_min / sn and > 0 and < 1

uk_max

double

-

relative short circuit voltage at maximum tap

❌ default same as uk

>= pk_max / sn and > 0 and < 1

pk_min

double

watt (W)

short circuit (copper) loss at minimum tap

❌ default same as pk

>= 0

pk_max

double

watt (W)

short circuit (copper) loss at maximum tap

❌ default same as pk

>= 0

r_grounding_from

double

ohm (Ω)

grounding resistance at from-side, if relevant

❌ default zero

x_grounding_from

double

ohm (Ω)

grounding reactance at from-side, if relevant

❌ default zero

r_grounding_to

double

ohm (Ω)

grounding resistance at to-side, if relevant

❌ default zero

x_grounding_to

double

ohm (Ω)

grounding reactance at to-side, if relevant

❌ default zero

Note

It can happen that tap_min > tap_max. In this case the winding voltage is decreased if the tap position is increased.

Electric Model

transformer is described by a \(\pi\) model, where \(Z_{\text{series}}\) can be computed as

\[\begin{split} \begin{eqnarray} & |Z_{\text{series}}| = \frac{u_k}{z_{\text{base}}} \\ & \mathrm{Re}(Z_{\text{series}}) = \frac{p_k / s_n}{z_{\text{base}}} \\ & \mathrm{Im}(Z_{\text{series}}) = \sqrt{|Z_{\text{series}}|^2-\mathrm{Re}(Z_{\text{series}})^2} \\ \end{eqnarray} \end{split}\]

and \(Y_{\text{shunt}}\) can be computed as

\[\begin{split} \begin{eqnarray} & |Y_{\text{shunt}}| = \frac{i_0}{y_{\text{base}}} \\ & \mathrm{Re}(Y_{\text{shunt}}) = \frac{s_n / p_0}{y_{\text{base}}} \\ & \mathrm{Im}(Y_{\text{shunt}}) = -\sqrt{|Y_{\text{shunt}}|^2-\mathrm{Re}(Y_{\text{shunt}})^2} \\ \end{eqnarray} \end{split}\]

where \(z_{\text{base}} = 1 / y_{\text{base}} = {u_{\text{2, rated}}}^2 / s_{\text{base}}\). Here, \(s_{\text{base}}\) is a constant value determined by the solver and \(u_{\text{2, rated}}\) is rated voltage at to_node.

Branch3

  • type name: branch3

  • base: Base

branch3 is the abstract base type for the component which connects three different nodes. For each branch3 three switches are always defined at side 1, 2, or 3 of the branch. In reality such switches may not exist.

Input

name

data type

unit

description

required

update

valid values

node_1

int32_t

-

ID of node at side 1

a valid node ID

node_2

int32_t

-

ID of node at side 2

a valid node ID

node_3

int32_t

-

ID of node at side 3

a valid node ID

status_1

int8_t

-

connection status at side 1

0 or 1

status_2

int8_t

-

connection status at side 2

0 or 1

status_3

int8_t

-

connection status at side 3

0 or 1

Steady state output

name

data type

unit

description

p_1

RealValueOutput

watt (W)

active power flowing into the branch at side 1

q_1

RealValueOutput

volt-ampere-reactive (var)

reactive power flowing into the branch at side 1

i_1

RealValueOutput

ampere (A)

current at side 1

s_1

RealValueOutput

volt-ampere (VA)

apparent power flowing at side 1

p_2

RealValueOutput

watt (W)

active power flowing into the branch at side 2

q_2

RealValueOutput

volt-ampere-reactive (var)

reactive power flowing into the branch at side 2

i_2

RealValueOutput

ampere (A)

current at side 2

s_2

RealValueOutput

volt-ampere (VA)

apparent power flowing at side 2

p_3

RealValueOutput

watt (W)

active power flowing into the branch at side 3

q_3

RealValueOutput

volt-ampere-reactive (var)

reactive power flowing into the branch at side 3

i_3

RealValueOutput

ampere (A)

current at side 3

s_3

RealValueOutput

volt-ampere (VA)

apparent power flowing at side 3

loading

double

-

relative loading of the branch, 1.0 meaning 100% loaded.

Short circuit output

name

data type

unit

description

i_1

RealValueOutput

ampere (A)

current at side 1

i_1_angle

RealValueOutput

rad

current angle at side 1

i_2

RealValueOutput

ampere (A)

current at side 2

i_2_angle

RealValueOutput

rad

current angle at side 2

i_3

RealValueOutput

ampere (A)

current at side 3

i_3_angle

RealValueOutput

rad

current angle at side 3

Three-Winding Transformer

three_winding_transformer is a Branch3 connects three nodes with possibly different voltage levels. An example of usage of three-winding transformer is given in Transformer Examples.

Input

name

data type

unit

description

required

update

valid values

u1

double

volt (V)

rated voltage at side 1

> 0

u2

double

volt (V)

rated voltage at side 2

> 0

u3

double

volt (V)

rated voltage at side 3

> 0

sn_1

double

volt-ampere (VA)

rated power at side 1

> 0

sn_2

double

volt-ampere (VA)

rated power at side 2

> 0

sn_3

double

volt-ampere (VA)

rated power at side 3

> 0

uk_12

double

-

relative short circuit voltage across side 1-2, 0.1 means 10%

>= pk_12 / min(sn_1, sn_2) and > 0 and < 1

uk_13

double

-

relative short circuit voltage across side 1-3, 0.1 means 10%

>= pk_13 / min(sn_1, sn_3) and > 0 and < 1

uk_23

double

-

relative short circuit voltage across side 2-3, 0.1 means 10%

>= pk_23 / min(sn_2, sn_3) and > 0 and < 1

pk_12

double

watt (W)

short circuit (copper) loss across side 1-2

>= 0

pk_13

double

watt (W)

short circuit (copper) loss across side 1-3

>= 0

pk_23

double

watt (W)

short circuit (copper) loss across side 2-3

>= 0

i0

double

-

relative no-load current with respect to side 1

>= p0 / sn and < 1

p0

double

watt (W)

no-load (iron) loss

>= 0

winding_1

WindingType

-

side 1 winding type

winding_2

WindingType

-

side 2 winding type

winding_3

WindingType

-

side 3 winding type

clock_12

int8_t

-

clock number of phase shift across side 1-2, odd number is only allowed for Dy(n) or Y(N)d configuration.

>= 0 and <= 12

clock_13

int8_t

-

clock number of phase shift across side 1-3, odd number is only allowed for Dy(n) or Y(N)d configuration.

>= 0 and <= 12

tap_side

Branch3Side

-

side of tap changer

side_1 or side_2 or side_3

tap_pos

int8_t

-

current position of tap changer

(tap_min <= tap_pos <= tap_max) or (tap_min >= tap_pos >= tap_max)

tap_min

int8_t

-

position of tap changer at minimum voltage

tap_max

int8_t

-

position of tap changer at maximum voltage

tap_nom

int8_t

-

nominal position of tap changer

❌ default zero

(tap_min <= tap_nom <= tap_max) or (tap_min >= tap_nom >= tap_max)

tap_size

double

volt (V)

size of each tap of the tap changer

> 0

uk_12_min

double

-

relative short circuit voltage at minimum tap, across side 1-2

❌ default same as uk_12

>= pk_12_min / min(sn_1, sn_2) and > 0 and < 1

uk_12_max

double

-

relative short circuit voltage at maximum tap, across side 1-2

❌ default same as uk_12

>= pk_12_max / min(sn_1, sn_2) and > 0 and < 1

pk_12_min

double

watt (W)

short circuit (copper) loss at minimum tap, across side 1-2

❌ default same as pk_12

>= 0

pk_12_max

double

watt (W)

short circuit (copper) loss at maximum tap, across side 1-2

❌ default same as pk_12

>= 0

uk_13_min

double

-

relative short circuit voltage at minimum tap, across side 1-3

❌ default same as uk_13

>= pk_13_min / min(sn_1, sn_3) and > 0 and < 1

uk_13_max

double

-

relative short circuit voltage at maximum tap, across side 1-3

❌ default same as uk_13

>= pk_13_max / min(sn_1, sn_3) and > 0 and < 1

pk_13_min

double

watt (W)

short circuit (copper) loss at minimum tap, across side 1-3

❌ default same as pk_13

>= 0

pk_13_max

double

watt (W)

short circuit (copper) loss at maximum tap, across side 1-3

❌ default same as pk_13

>= 0

uk_23_min

double

-

relative short circuit voltage at minimum tap, across side 2-3

❌ default same as uk_23

>= pk_23_min / min(sn_2, sn_3) and > 0 and < 1

uk_23_max

double

-

relative short circuit voltage at maximum tap, across side 2-3

❌ default same as uk_23

>= pk_23_max / min(sn_2, sn_3) and > 0 and < 1

pk_23_min

double

watt (W)

short circuit (copper) loss at minimum tap, across side 2-3

❌ default same as pk_23

>= 0

pk_23_max

double

watt (W)

short circuit (copper) loss at maximum tap, across side 2-3

❌ default same as pk_23

>= 0

r_grounding_1

double

ohm (Ω)

grounding resistance at side 1, if relevant

❌ default zero

x_grounding_1

double

ohm (Ω)

grounding reactance at side 1, if relevant

❌ default zero

r_grounding_2

double

ohm (Ω)

grounding resistance at side 2, if relevant

❌ default zero

x_grounding_2

double

ohm (Ω)

grounding reactance at side 2, if relevant

❌ default zero

r_grounding_3

double

ohm (Ω)

grounding resistance at side 3, if relevant

❌ default zero

x_grounding_3

double

ohm (Ω)

grounding reactance at side 3, if relevant

❌ default zero

Note

It can happen that tap_min > tap_max. In this case the winding voltage is decreased if the tap position is increased.

Electric Model

three_winding_transformer is modelled as 3 transformers of pi model each connected together in star configuration. However, there are only 2 pi “legs”: One at side_1 and one in the centre of star. The values between windings (for e.g., uk_12 or pk_23) are converted from delta to corresponding star configuration values. The calculation of series and shunt admittance from uk, pk, i0 and p0 is same as mentioned in Transformer.

Appliance

  • type name: appliance

  • base: Base

appliance is an abstract user which is coupled to a node. For each appliance a switch is defined between the appliance and the node. The reference direction for power flows is mentioned in Reference Direction.

Input

name

data type

unit

description

required

update

valid values

node

int32_t

-

ID of the coupled node

a valid node ID

status

int8_t

-

connection status to the node

0 or 1

Steady state output

name

data type

unit

description

p

RealValueOutput

watt (W)

active power

q

RealValueOutput

volt-ampere-reactive (var)

reactive power

i

RealValueOutput

ampere (A)

current

s

RealValueOutput

volt-ampere (VA)

apparent power

pf

RealValueOutput

-

power factor

Short circuit output

name

data type

unit

description

i

RealValueOutput

ampere (A)

current

i_angle

RealValueOutput

rad

current angle

Source

source is an Appliance representing the external network with a Thévenin’s equivalence. It has an infinite voltage source with an internal impedance. The impedance is specified by convention as short circuit power.

Input

name

data type

unit

description

required

update

valid values

u_ref

double

-

reference voltage in per-unit

✨ only for power flow

> 0

u_ref_angle

double

rad

reference voltage angle

❌ default 0.0

sk

double

volt-ampere (VA)

short circuit power

❌ default 1e10

> 0

rx_ratio

double

-

R to X ratio

❌ default 0.1

>= 0

z01_ratio

double

-

zero sequence to positive sequence impedance ratio

❌ default 1.0

> 0

Electric Model

source is modeled by an internal constant impedance \(r+\mathrm{j}x\) with positive sequence and zero sequence. Its value can be computed using following equations:

  • for positive sequence,

\[\begin{split} \begin{eqnarray} & z_{\text{source}} = \frac{s_{\text{base}}}{s_k} \\ & x_1 = z_{\text{source}} \sqrt{1+ \left(\frac{r}{x}\right)^2} \\ & r_1 = x_1 \cdot \left(\frac{r}{x}\right)^2 \end{eqnarray} \end{split}\]

where \(s_{\text{base}}\) is a constant value determined by the solver, and \(\frac{r}{x}\) indicates rx_ratio as input.

  • for zero sequence,

\[\begin{split} \begin{eqnarray} & z_{\text{source,0}} = z_{\text{source}} \cdot \frac{z_0}{z_1}\\ & x_0 = z_{\text{source,0}} \sqrt{1 + \left(\frac{r}{x}\right)^2}\\ & r_0 = x_0 \cdot \left(\frac{r}{x}\right)^2 \end{eqnarray} \end{split}\]

Generic Load and Generator

  • type name: generic_load_gen

generic_load_gen is an abstract load/generation Appliance which contains only the type of the load/generation with response to voltage.

name

data type

unit

description

required

update

type

LoadGenType

-

type of load/generator with response to voltage

Load/Generator Concrete Types

There are four concrete types of load/generator. They share similar attributes: specified active/reactive power. However, the reference direction and meaning of RealValueInput is different, as shown in the table below.

type name

reference direction

meaning of RealValueInput

sym_load

load

double

sym_gen

generator

double

asym_load

load

double[3]

asym_gen

generator

double[3]

Input

name

data type

unit

description

required

update

p_specified

RealValueInput

watt (W)

specified active power

✨ only for power flow

q_specified

RealValueInput

volt-ampere-reactive (var)

specified reactive power

✨ only for power flow

Electric model

generic_load_gen is modelled by using the so-called ZIP load model in power-grid-model, where a load/generator is represented as a composition of constant power (P), constant current (I) and constant impedance (Z).

The injection of each ZIP model type can be computed as follows:

  • for a constant impedance (Z) load/generator,

\[ \begin{eqnarray} S = S_{\text{specified}} \cdot \bar{u}^2 \end{eqnarray} \]
  • for a constant current (I) load/generator,

\[ \begin{eqnarray} S = S_{\text{specified}} \cdot \bar{u} \end{eqnarray} \]
  • for a constant power (P) load/generator:,

\[ \begin{eqnarray} S = S_{\text{specified}} \end{eqnarray} \]

where \(\bar{u}\) is the calculated node voltage.

Shunt

shunt is an Appliance with a fixed admittance (impedance). It behaves similar to a load/generator with type const_impedance.

Input

name

data type

unit

description

required

update

g1

double

siemens (S)

positive-sequence shunt conductance

b1

double

siemens (S)

positive-sequence shunt susceptance

g0

double

siemens (S)

zero-sequence shunt conductance

✨ only for asymmetric calculation

b0

double

siemens (S)

zero-sequence shunt susceptance

✨ only for asymmetric calculation

Note

In case of short circuit calculations, the zero-sequence parameters are required only if any of the faults in any of the scenarios within a batch are not three-phase faults (i.e. fault_type is not FaultType.three_phase).

Electric Model

shunt is modelled by a fixed admittance which equals to \(g + \mathrm{j}b\).

Sensor

  • type name: sensor

  • base: Base

sensor is an abstract type for all the sensor types. A sensor does not have any physical meaning. Rather, it provides measurement data for the state estimation algorithm. The state estimator uses the data to evaluate the state of the grid with the highest probability.

Input

name

data type

unit

description

required

update

valid values

measured_object

int32_t

-

ID of the measured object

a valid object ID

Generic Voltage Sensor

  • type name: generic_voltage_sensor

generic_voltage_sensor is an abstract class for symmetric and asymmetric voltage sensor and derived from Sensor. It measures the magnitude and (optionally) the angle of the voltage of a node.

Input

name

data type

unit

description

required

update

valid values

u_sigma

double

volt (V)

standard deviation of the measurement error. Usually this is the absolute measurement error range divided by 3.

✨ only for state estimation

> 0

Voltage Sensor Concrete Types

There are two concrete types of voltage sensor. They share similar attributes: the meaning of RealValueInput is different, as shown in the table below. In a sym_voltage_sensor the measured voltage is a line-to-line voltage. In a asym_voltage_sensor the measured voltage is a 3-phase line-to-ground voltage.

type name

meaning of RealValueInput

sym_voltage_sensor

double

asym_voltage_sensor

double[3]

Input

name

data type

unit

description

required

update

valid values

u_measured

RealValueInput

volt (V)

measured voltage magnitude

✨ only for state estimation

> 0

u_angle_measured

RealValueInput

rad

measured voltage angle (only possible with phasor measurement units)

Steady state output

name

data type

unit

description

u_residual

RealValueOutput

volt (V)

residual value between measured voltage magnitude and calculated voltage magnitude

u_angle_residual

RealValueOutput

rad

residual value between measured voltage angle and calculated voltage angle (only possible with phasor measurement units)

Electric Model

generic_voltage_sensor is modeled by following equations:

\[\begin{split} \begin{eqnarray} & u_{\text{residual}} = u_{\text{measured}} - u_{\text{state}} \\ & \theta_{\text{residual}} = \theta_{\text{measured}} - \theta_{\text{state}} \end{eqnarray} \end{split}\]

Generic Power Sensor

  • type name: generic_power_sensor

power_sensor is an abstract class for symmetric and asymmetric power sensor and is derived from Sensor. It measures the active/reactive power flow of a terminal. The terminal is either connecting an appliance and a node, or connecting the from/to end of a branch (except link) and a node. In case of a terminal between an appliance and a node, the power Reference Direction in the measurement data is the same as the reference direction of the appliance. For example, if a power_sensor is measuring a source, a positive p_measured indicates that the active power flows from the source to the node.

Note

  1. Due to the high admittance of a link it is chosen that a power sensor cannot be coupled to a link, even though a link is a branch

  2. The node injection power sensor gets placed on a node. In the state estimation result, the power from this injection is distributed equally among the connected appliances at that node. Because of this distribution, at least one appliance is required to be connected to the node where an injection sensor is placed for it to function.

Input

name

data type

unit

description

required

update

valid values

measured_terminal_type

MeasuredTerminalType

-

indicate if it measures an appliance or a branch

the terminal type should match the measured_object

power_sigma

double

volt-ampere (VA)

standard deviation of the measurement error. Usually this is the absolute measurement error range divided by 3. See Power Sensor Concrete Types.

✨ in certain cases for state estimation. See the explanation for concrete types below.

> 0

Power Sensor Concrete Types

There are two concrete types of power sensor. They share similar attributes: the meaning of RealValueInput is different, as shown in the table below.

type name

meaning of RealValueInput

sym_power_sensor

double

asym_power_sensor

double[3]

Input

name

data type

unit

description

required

update

p_measured

RealValueInput

watt (W)

measured active power

✨ only for state estimation

q_measured

RealValueInput

volt-ampere-reactive (var)

measured reactive power

✨ only for state estimation

p_sigma

RealValueInput

watt (W)

standard deviation of the active power measurement error. Usually this is the absolute measurement error range divided by 3.

❌ see the explanation below.

q_sigma

RealValueInput

volt-ampere-reactive (var)

standard deviation of the reactive power measurement error. Usually this is the absolute measurement error range divided by 3.

❌ see the explanation below.

Valid combinations of power_sigma, p_sigma and q_sigma are:

power_sigma

p_sigma

q_sigma

result

x

x

x

x

x

x

x

x

x

x

x

x

Note

  1. If both p_sigma and q_sigma are provided, they represent the standard deviation of the active and reactive power, respectively, and the value of power_sigma is ignored. Any infinite component invalidates the entire measurement.

  2. If neither p_sigma nor q_sigma are provided, power_sigma represents the standard deviation of the apparent power.

  3. Providing only one of p_sigma and q_sigma results in undefined behaviour.

See the documentation on state estimation calculation methods for details per method on how the variances are taken into account for both the active and reactive power and for the individual phases.

Steady state output

name

data type

unit

description

p_residual

RealValueOutput

watt (W)

residual value between measured active power and calculated active power

q_residual

RealValueOutput

volt-ampere-reactive (var)

residual value between measured reactive power and calculated reactive power

Electric Model

Generic Power Sensor is modeled by following equations:

\[\begin{split} \begin{eqnarray} & p_{\text{residual}} = p_{\text{measured}} - p_{\text{state}} \\ & q_{\text{residual}} = q_{\text{measured}} - q_{\text{state}} \end{eqnarray} \end{split}\]

Fault

  • type name: fault

fault defines a short circuit location in the grid. At this moment a fault can only happen at a node.

Input

name

data type

unit

description

required

update

valid values

status

int8_t

-

whether the fault is active

0 or 1

fault_type

FaultType

-

the type of the fault

✨ only for short circuit

fault_phase

FaultPhase

-

the phase(s) of the fault

❌ default FaultPhase.default_value (see below)

fault_object

int32_t

-

ID of the component where the short circuit happens

A valid node ID

r_f

double

ohm (Ω)

short circuit resistance

❌ default 0.0

x_f

double

ohm (Ω)

short circuit reactance

❌ default 0.0

Note

Multiple faults may exist within one calculation. Currently, all faults in one scenario are required to have the same fault_type and fault_phase. Across scenarios in a batch, the fault_type and fault_phase may differ.

Note

If any of the faults in any of the scenarios within a batch are not three_phase (i.e. fault_type is not FaultType.three_phase), the calculation is treated as asymmetric.

Steady state output

A fault has no steady state output.

Short circuit output

name

data type

unit

description

i_f

RealValueOutput

ampere (A)

current

i_f_angle

RealValueOutput

rad

current angle

Electric Model

Four types of short circuit fault are included in power-grid-model.

fault_type

fault_phase

description

FaultType.three_phase

FaultPhase.abc

Three phases are connected with fault impedance.

FaultType.single_phase_to_ground

FaultPhase.a

One phase is grounded with fault impedance, and other phases are open.

FaultType.two_phase

FaultPhase.bc

Two phases are connected with fault impedance.

FaultType.two_phase_to_ground

FaultPhase.bc

Two phases are connected with fault impedance then grounded.

In case the fault_phase is not specified or is equal to FaultPhase.default_value, the power-grid-model assumes the following fault phases for different values of fault_type.